Active chlorine sensors

sonde de chlore actif CAA2563 - 69 0-2 ppm

Active Chlorine sensors : CAA2563 – 69
2 – 10 ppm / 70°C 8 Bars – Special SANITARY HOT WATER

CAA2563 and CAA2569 sensors for sanitary hot water are used to measure active chlorine, ie hypochlorous acid and chlorine dioxide in sanitary hot water. Specially adapted for chlorine measurement in pressure and used for legionella chlorine treatment.

Advantages:

  • Amperometric measurement
  • Continuous accurate and reliable analysis
  • Fast execution

Applications

  • Sanitary hot water
Measure
  • Active chlorine HOCl
Measurement range
  • 0 – 2 ppm (CAA2563)
  • 0 – 10 ppm (CAA2569)
pH range
  • 5 – 9 pH
Temperature range
  • 40 – 50°C
Interference
  • Chlorine dioxide (4x)
  • Chlorites
  • Ozone (9x)
Maximum pressure and
supply flow
  • 8 bars
  • Mini: 20 l/h
  • Maxi: 80 l/h
  • Recommanded: 30 l/h
Starting time and
definitive calibration
  • First calibration after 2 h
  • After 24 h
Membrane cap lifetime 
  • Currently 1 year (according to water quality)
Membrane
  • Without
Material and
protection type
  • Beige PPE
  • IP 65
Supply voltage and
output signal
  • 10 – 25 VDC
  • 4-20 mA

For more information

For more information

Price request